ABB MNS-MCC Error Code E-111

ABB Electrical Major Contactor

Model: MNS-MCC | Code: E-111

Applicable Systems
MNS-MCC

Symptoms

The motor contactor has failed to close when commanded. The motor does not start and the control circuit shows 0V at the contactor coil terminals.

Possible Causes

  • Control circuit fuse blown due to a short or overload in the control wiring
  • Contactor coil open-circuited from overheating or age
  • Control relay or PLC output failed to energize the contactor coil
  • Emergency stop circuit open, breaking the control power to the contactor

Troubleshooting Steps

  1. Step 1: Check the control circuit fuse for continuity
    Replace if blown; investigate for shorts before re-energizing
  2. Step 2: Measure the voltage at the contactor coil terminals when a start command is given
    If voltage is present but the contactor does not close, the coil is faulty
  3. Step 3: Measure the coil resistance with power off and compare to the nameplate value
    Replace the contactor if the coil is open or shorted
  4. Step 4: Trace the control circuit from the PLC output through all interlocks to find the open point
    Check emergency stops, overload auxiliary contacts, and interlock relays

How to Reset

Reset: After replacing the fuse, coil, or fixing the control circuit, the contactor closes normally on the next start command.

Common Replacement Parts

  • Contactor coil: 24V DC or 120V AC, match to existing (Verify coil voltage before ordering)
  • Control circuit fuse: 2A or 5A, time-delay type (Match to existing fuse class)
  • Control relay: Ice-cube or plug-in type, 8-pin (Match socket and coil voltage)

Frequently Asked Questions

  • Q: How do I test a contactor coil?

    With power off, measure resistance across the coil terminals. A reading of infinity means the coil is open. Compare to the nameplate resistance.

  • Q: What causes a control fuse to blow?

    Shorted wiring, failed coil, or jammed contactor mechanism. Inspect for wire chafing and terminal shorts before replacing the fuse.

  • Q: Can I replace just the coil?

    On some contactors, yes. Check if the manufacturer offers a coil-only spare part. If not, replace the entire contactor.