APC Smart-UPS Error Code A027

APC UPS Major Alarm

Model: Smart-UPS | Code: A027

Applicable Systems
Symmetra LX

Symptoms

The neutral connection is missing on the UPS input. Output voltage may be unstable.

Possible Causes

  • Neutral wire disconnected or broken
  • Neutral bonding issue in the distribution panel

Troubleshooting Steps

  1. Step 1: Check the neutral connection at the UPS input
    Neutral wire is disconnected
  2. Step 2: Reconnect the neutral wire and verify continuity
    Neutral connection is restored

How to Reset

To reset: Restore the neutral connection, then restart the UPS.

Source: APC Smart-UPS User Manual, Schneider Electric/APC

Category: UPS