Bosch Rexroth IndraDrive Error Code C0260

Bosch Rexroth PLC & VFD Major Motor

Model: IndraDrive | Code: C0260

Applicable Systems
IndraDrive

Symptoms

The IndraDrive reports a motor phase loss fault. One or more motor output phases are missing, causing unbalanced motor operation.

Possible Causes

  • Motor cable disconnected or broken on one phase
  • Motor terminal box loose connection on one phase
  • Drive output phase failure due to semiconductor damage

Troubleshooting Steps

  1. Step 1: Check all motor cable connections at the drive and motor ends
    All phase connections are tight and secure
  2. Step 2: Measure motor winding resistance between all three phases for balance
    All phase resistances are balanced
  3. Step 3: If the drive output is faulty, replace the drive unit
    Drive output is balanced on all three phases

How to Reset

To reset: Restore all three motor output phases, then reset the fault.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Bosch Rexroth IndraDrive Functional Description, Bosch Rexroth AG

Category: PLC & VFD