Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E13

Copeland Refrigeration Major Pressure

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E13

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor reports a system high-pressure switch trip. The high-pressure safety switch has activated, cutting power to the compressor control circuit.

Possible Causes

  • Condenser water flow insufficient in water-cooled systems
  • Cooling tower performance degraded or offline
  • Refrigerant overcharge raising condensing pressure

Troubleshooting Steps

  1. Step 1: Check condenser water flow rate and pump operation
    Flow rate meets the design specification
  2. Step 2: Verify cooling tower fan and fill condition
    Tower delivers design approach temperature
  3. Step 3: Check refrigerant charge by subcooling measurement
    Subcooling is within the specified range

How to Reset

To reset: Resolve the high-pressure condition, then manually reset the high-pressure switch.