Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E1

Copeland Refrigeration Critical Power

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E1

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor reports a power phase reversal error. The scroll compressor will not start or runs in reverse rotation, causing loud noise and no pumping.

Possible Causes

  • Power supply phase sequence reversed at the compressor terminals
  • Incorrect wiring during installation or maintenance

Troubleshooting Steps

  1. Step 1: Check the phase sequence at the compressor power supply terminals using a phase rotation tester
    Correct phase sequence L1-L2-L3 is confirmed
  2. Step 2: Swap any two incoming power leads to correct the phase sequence
    Phase sequence tester shows correct rotation direction

How to Reset

To reset: Correct the phase sequence at the power supply, then cycle the compressor power off and on.

Source: Copeland Scroll Compressor Service Manual, Emerson Climate Technologies

Category: Refrigeration