Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E1

Copeland Refrigeration Critical Power

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E1

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor reports a power phase reversal error. The scroll compressor will not start or runs in reverse rotation, causing loud noise and no pumping.

Possible Causes

  • Power supply phase sequence reversed at the compressor terminals
  • Incorrect wiring during installation or maintenance

Troubleshooting Steps

  1. Step 1: Check the phase sequence at the compressor power supply terminals using a phase rotation tester
    Correct phase sequence L1-L2-L3 is confirmed
  2. Step 2: Swap any two incoming power leads to correct the phase sequence
    Phase sequence tester shows correct rotation direction

How to Reset

To reset: Correct the phase sequence at the power supply, then cycle the compressor power off and on.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Copeland Scroll Compressor Service Manual, Emerson Climate Technologies

Category: Refrigeration