Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E2

Copeland Refrigeration Critical Pressure

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E2

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor trips on high-low pressure protection. The system pressure has exceeded the safety threshold and the compressor shuts down to prevent damage.

Possible Causes

  • Condenser fouling or insufficient airflow causing high discharge pressure
  • Evaporator icing or restricted airflow causing low suction pressure
  • Refrigerant charge incorrect - overcharge or undercharge

Troubleshooting Steps

  1. Step 1: Check condenser condition and verify fan operation
    Condenser is clean and fans run at full speed
  2. Step 2: Check suction and discharge pressure gauges against normal operating range
    Pressures are within manufacturer specified range
  3. Step 3: Verify refrigerant charge level using subcooling and superheat measurements
    Charge quantity matches the nameplate value

How to Reset

To reset: Resolve the pressure abnormality, then press the manual reset button on the pressure control.

Source: Copeland Scroll Compressor Service Manual, Emerson Climate Technologies

Category: Refrigeration