Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E14

Copeland Refrigeration Major Pressure

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E14

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor reports a system low-pressure switch trip. The low-pressure safety switch has activated, cutting power to protect the compressor from low suction conditions.

Possible Causes

  • Refrigerant leak causing low system charge
  • Evaporator load too low for the compressor capacity
  • Expansion valve stuck closed or capillary tube blocked

Troubleshooting Steps

  1. Step 1: Perform a thorough leak inspection of all joints and fittings
    Leaks are found and repaired
  2. Step 2: Verify the evaporator heat load is sufficient for the compressor
    Load matches the compressor capacity range
  3. Step 3: Check expansion valve bulb attachment and superheat setting
    Valve operates correctly with proper superheat

How to Reset

To reset: Raise suction pressure above the threshold, then reset the low-pressure switch.

Source: Copeland Scroll Compressor Service Manual, Emerson Climate Technologies

Category: Refrigeration