Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E19

Copeland Refrigeration Major Control

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E19

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor reports a contactor fault. The main contactor has failed to pull in or has welded contacts, preventing proper compressor control.

Possible Causes

  • Contactor coil burned out or open circuited
  • Contactor contacts welded shut from arcing
  • Control circuit voltage low preventing contactor pickup

Troubleshooting Steps

  1. Step 1: Test the contactor coil for continuity and proper resistance
    Coil resistance matches the rated value
  2. Step 2: Inspect contacts for pitting, welding, or excessive wear
    Contacts are clean and make positive contact
  3. Step 3: Verify control circuit voltage at the contactor coil
    Voltage is within 10 percent of rated coil voltage

How to Reset

To reset: Replace the faulty contactor or restore control voltage, then reset the safety circuit.