Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E5

Copeland Refrigeration Critical Motor

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E5

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor trips on motor overload. The motor current has exceeded the rated value for an extended period, activating the overload protection.

Possible Causes

  • Compressor running outside design conditions with excessive load
  • Low supply voltage causing high motor current
  • Shorted motor windings or partial ground fault

Troubleshooting Steps

  1. Step 1: Check motor current with a clamp meter and compare to nameplate FLA
    Current is at or below the nameplate full load amps
  2. Step 2: Verify supply voltage at the compressor terminals under load
    Voltage is within 10 percent of rated value
  3. Step 3: Megger test the motor windings for insulation integrity
    Insulation resistance exceeds 100 megohms

How to Reset

To reset: Clear the overload condition, allow the motor to cool, then press the overload reset button.