Eaton PowerXL DG1 Error Code F2

Eaton PLC & VFD Critical Overvoltage

Model: PowerXL DG1 | Code: F2

Applicable Systems
9395

Symptoms

Overvoltage: DC link voltage exceeds limit.

Possible Causes

  • Deceleration too fast
  • No brake chopper
  • Mains voltage too high

Troubleshooting Steps

  1. Step 1: Increase deceleration time
    No overvoltage trip
  2. Step 2: Connect brake resistor
    DC link voltage controlled
  3. Step 3: Check mains voltage
    Voltage within rated range

How to Reset

Reset via control panel after resolving overvoltage.

Source: Eaton PowerXL DG1 Troubleshooting Guide, Eaton Corporation

Category: PLC & VFD