Eaton PowerXL DG1 Error Code F2

Eaton PLC & VFD Critical Overvoltage

Model: PowerXL DG1 | Code: F2

Applicable Systems
9395

Symptoms

Overvoltage: DC link voltage exceeds limit.

Possible Causes

  • Deceleration too fast
  • No brake chopper
  • Mains voltage too high

Troubleshooting Steps

  1. Step 1: Increase deceleration time
    No overvoltage trip
  2. Step 2: Connect brake resistor
    DC link voltage controlled
  3. Step 3: Check mains voltage
    Voltage within rated range

How to Reset

Reset via control panel after resolving overvoltage.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Eaton PowerXL DG1 Troubleshooting Guide, Eaton Corporation

Category: PLC & VFD