Fatek FBs Communication Error Code 5

Fatek PLC & VFD Critical Program

Model: FBs | Code: 5

Applicable Systems
FBs-MA FBs-MC FBs-MN B1 HB1

Symptoms

When attempting to run the PLC, a ladder logic checksum mismatch is detected. The PLC cannot enter RUN mode and returns error code 5 to indicate that the ladder program integrity check has failed.

Possible Causes

  • Ladder program corruption due to power interruption during program write
  • Memory module degradation or hardware fault
  • Mismatch between the program stored in flash and the working copy in RAM

Troubleshooting Steps

  1. Step 1: Connect to the PLC using WinProladder software and attempt to read the ladder program
    Software can communicate with the PLC and display the program contents
  2. Step 2: If the program reads correctly, recompile and download it to the PLC to refresh the checksum
    Download completes successfully and checksum is recalculated
  3. Step 3: If the program cannot be read, restore from a known-good backup file
    Backup program downloads successfully and PLC enters RUN mode
  4. Step 4: If the problem persists after restoring the program, replace the CPU module or memory cartridge
    New hardware accepts the program and passes checksum verification

How to Reset

To reset: 1) Re-download the ladder program using WinProladder. 2) Cycle power to the PLC. 3) Attempt to enter RUN mode. If the error persists, replace the memory module.

Common Replacement Parts

  • FBs-CM55E: Memory cartridge for FBs series PLC (Verify compatibility with the specific CPU model before replacement)

Frequently Asked Questions

  • Q: What causes a ladder checksum error on FATEK PLC?

    Typically caused by program corruption from power loss during write operations, or memory hardware degradation. Re-downloading the program usually resolves it.

  • Q: Can I recover the program from a PLC with a checksum error?

    If WinProladder can still communicate with the PLC, you may be able to upload the program. If not, you must restore from a backup file.

Source: FATEK FBs Communication Protocol Manual, Appendix 1

Category: PLC & VFD