Fuji FRENIC Error Code 036

Fuji PLC & VFD Major Overvoltage

Model: FRENIC | Code: 036

Applicable Systems
FRENIC

Symptoms

The FRENIC reports a DC bus overvoltage fault at constant speed detected. The drive trips to protect the capacitor bank and switching devices.

Possible Causes

  • Regenerative energy from the motor exceeded the braking resistor capacity
  • Deceleration time too short causing excessive regenerative voltage
  • Input power supply voltage at the upper limit of the drive range

Troubleshooting Steps

  1. Step 1: Increase the deceleration time to reduce regenerative energy
    DC bus voltage stays below the trip threshold
  2. Step 2: Check if a braking resistor is installed and correctly rated
    Braking resistor absorbs regenerative energy adequately
  3. Step 3: Measure the input supply voltage and verify it is within range
    Input voltage is within the drive rated range

How to Reset

To reset: Reduce the DC bus voltage below the threshold, then reset the fault.