Applicable Systems
AKD

Symptoms

The AKD reports a data backup failure. The parameter backup operation to non-volatile memory did not complete successfully.

Possible Causes

  • Power loss during the EEPROM write cycle
  • EEPROM memory cell degradation due to excessive write cycles
  • Internal data bus error during the backup operation

Troubleshooting Steps

  1. Step 1: Retry the backup operation with stable power in the drive
    Backup completes successfully on retry
  2. Step 2: If the error recurs, reload default parameters and reconfigure
    Parameters are restored to known-good values
  3. Step 3: If the EEPROM is defective, replace the drive unit
    New unit backs up data without errors

How to Reset

To reset: Retry the backup with stable power, then cycle power.

Source: Kollmorgen AKD Drive Manual, Kollmorgen Corporation