Mitsubishi iQ-R Motion Controller Error Code 1FE1H (Details: 0103H)

Mitsubishi PLC & VFD Moderate Error Motion Control

Model: iQ-R Motion Controller (R32MTCPU/R16MTCPU) | Code: 1FE1H (Details: 0103H)

Applicable Systems
MELSEC FX3U MELSEC FX5U FR-A800 FR-A700 MR-J4 iQ-R Motion Controller (R32MTCPU/R16MTCPU)

Symptoms

Machine configuration error or machine library error. Parameter block specification incorrect. The machine does not start. Error code 1FE1H/30FAH with details code 0103H.

Possible Causes

  • The specification of the parameter block No. of the machine speed setting is outside the range of 1 to 64.

Troubleshooting Steps

  1. Step 1: Set the parameter block specification within the range of 1 to 64.
    Refer to manual for details

How to Reset

Reset using [Rq.2240] Machine error reset command (M43616+32m) or Error reset (SM50). Clear the root cause before resetting.

Source: MELSEC iQ-R Motion Controller Programming Manual IB-0300309-L, Appendix 2 & 3

Category: PLC & VFD