Applicable Systems
MELSEC FX3U
MELSEC FX5U
FR-A800
FR-A700
MR-J4
iQ-R Motion Controller (R32MTCPU/R16MTCPU)
Symptoms
Machine configuration error or machine library error. End point overflow. The machine does not start. Error code 1FE1H/30FAH with details code 0603H.
Possible Causes
- The point block specified in the positioning point is world/base/tool coordinate system, and the specified address is outside the range for 32-bit integer (signed).
Troubleshooting Steps
- Step 1: Correct the address of the point block specified in the positioning point, or correct the base translation value setting.
Refer to manual for details
How to Reset
Reset using [Rq.2240] Machine error reset command (M43616+32m) or Error reset (SM50). Clear the root cause before resetting.
Source: MELSEC iQ-R Motion Controller Programming Manual IB-0300309-L, Appendix 2 & 3
Category: PLC & VFD