Toshiba VF-AS1 Error Code E34

Toshiba PLC & VFD Major Torque

Model: VF-AS1 | Code: E34

Applicable Systems
VF-AS1

Symptoms

The VF-AS1 reports an under-torque fault. The motor torque dropped below the configured under-torque detection level.

Possible Causes

  • Mechanical load suddenly reduced or disconnected
  • Belt or coupling break causing loss of load torque
  • Under-torque detection level set too high for the application

Troubleshooting Steps

  1. Step 1: Check the mechanical load and coupling for disconnection
    Load is properly connected
  2. Step 2: Verify the under-torque detection level is appropriate
    Detection level matches the normal operating torque
  3. Step 3: Reduce the under-torque level if it is set too high
    Level is set below normal operating torque

How to Reset

To reset: Restore the load torque above the level, then reset.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Toshiba VF-AS1 Inverter Manual, Toshiba Mitsubishi-Electric Industrial Systems

Category: PLC & VFD