Toshiba VF-AS1 Error Code E21

Toshiba PLC & VFD Major Undervoltage

Model: VF-AS1 | Code: E21

Applicable Systems
VF-AS1

Symptoms

The VF-AS1 reports a DC bus undervoltage fault. The drive trips because the bus voltage dropped below the minimum operating level.

Possible Causes

  • Input power supply voltage dip or momentary outage
  • Power supply capacity insufficient for the drive load
  • Loose or corroded power wiring connection causing voltage drop

Troubleshooting Steps

  1. Step 1: Measure the input supply voltage during operation with a power analyzer
    Voltage remains stable within the rated range
  2. Step 2: Tighten all power wiring connections at the drive terminals
    All connections are tight with no voltage drop
  3. Step 3: If power dips are frequent, install a voltage stabilizer or UPS
    Supply voltage is stable and above the minimum

How to Reset

To reset: Restore the supply voltage to the rated range, then reset the fault.