Toshiba VF-AS1 Error Code E35

Toshiba PLC & VFD Major Control

Model: VF-AS1 | Code: E35

Applicable Systems
VF-AS1

Symptoms

The VF-AS1 reports a PID feedback loss fault. The process feedback signal for PID control was lost or went out of range.

Possible Causes

  • PID feedback sensor disconnected or failed
  • Feedback signal wiring broken or shorted
  • Feedback signal exceeded the configured input range

Troubleshooting Steps

  1. Step 1: Check the PID feedback sensor and its connection to the drive
    Sensor is connected and functioning
  2. Step 2: Measure the feedback signal voltage or current at the input terminal
    Signal is within the configured range
  3. Step 3: Replace the feedback sensor if it is defective
    New sensor provides a stable feedback signal

How to Reset

To reset: Restore the PID feedback signal, then reset the fault.

Source: Toshiba VF-AS1 Inverter Manual, Toshiba Mitsubishi-Electric Industrial Systems

Category: PLC & VFD