Applicable Systems
RTAC 200

Symptoms

Phase loss or phase sequence fault. The three-phase power supply has a missing or reversed phase.

Possible Causes

  • One phase wire disconnected or breaker tripped
  • Phase wiring reversed during installation

Troubleshooting Steps

  1. Step 1: Check all three phase voltages at the unit
    One phase is missing or voltage is unbalanced
  2. Step 2: Verify the phase sequence with a phase rotation tester
    Phase sequence is incorrect

How to Reset

To reset: Restore all phases and correct the sequence, then reset the controller.