Trane RTAC 200 Error Code E02

Trane Chiller Major Condenser

Model: RTAC 200 | Code: E02

Applicable Systems
RTAC 200

Symptoms

The Trane RTAC chiller displays alarm E02, indicating high discharge pressure. The refrigerant discharge pressure has exceeded the safety limit.

Possible Causes

  • Condenser coils dirty or fouled reducing heat rejection
  • Condenser fan motors not operating or running in wrong direction
  • Refrigerant overcharged causing excessive system pressure
  • High ambient temperature reducing condenser capacity

Troubleshooting Steps

  1. Step 1: Clean condenser coils and verify airflow is unobstructed
    Coils should be free of dirt, debris, and obstructions; use coil cleaner if necessary
  2. Step 2: Check all condenser fan motors are running
    Each fan should start and run at full speed; check fuses and contactors for failed fans
  3. Step 3: Verify refrigerant charge level against nameplate data
    Overcharge increases discharge pressure; recover excess refrigerant if overcharged
  4. Step 4: Check ambient temperature at condenser intake
    If ambient exceeds design conditions, consider additional ventilation or shading

How to Reset

To reset: 1) Clean condenser and verify fan operation. 2) Press reset on the control panel. 3) Monitor discharge pressure during operation. Caution: Repeated high discharge pressure alarms can activate the safety relief valve and cause refrigerant loss.

Frequently Asked Questions

  • Q: What discharge pressure triggers E02?

    E02 triggers when the discharge pressure exceeds the high-pressure safety switch setting, typically around 425 PSIG for R-134a systems. Refer to the specific model manual for exact thresholds.

  • Q: Can I reduce the high-pressure limit setting to prevent E02?

    No. The high-pressure safety limit is factory-set and must not be adjusted. The root cause of high discharge pressure must be addressed.