Bitzer Screw Compressor CSH/CSN Error Code AL11

Bitzer Refrigeration Critical Safety

Model: Screw Compressor CSH/CSN | Code: AL11

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports that the safety valve has opened. The system pressure exceeded the safety valve setpoint and the valve has relieved pressure.

Possible Causes

  • Excessive system pressure from condenser failure
  • Safety valve setpoint drifted below normal operating pressure
  • Safety valve seat damaged causing premature opening

Troubleshooting Steps

  1. Step 1: Investigate the cause of excessive pressure and correct it
    System pressure returns to normal range
  2. Step 2: Verify the safety valve setpoint against the specification
    Valve setpoint matches the design pressure
  3. Step 3: Replace the safety valve if it does not reseat properly
    New valve seals and holds pressure correctly

How to Reset

To reset: Resolve the overpressure condition, replace or reseat the safety valve, then reset the alarm.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH

Category: Refrigeration