Bitzer Screw Compressor CSH/CSN Error Code AL10

Bitzer Refrigeration Major Control

Model: Screw Compressor CSH/CSN | Code: AL10

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports a capacity control fault. The capacity control system is not responding or has lost position feedback.

Possible Causes

  • Capacity control solenoid valve stuck or coil failed
  • Capacity control linkage binding or mechanically jammed
  • Control pressure to the capacity regulator is insufficient

Troubleshooting Steps

  1. Step 1: Test capacity control solenoid valve coils for continuity
    Solenoid coils show proper resistance
  2. Step 2: Inspect the capacity control linkage for free movement
    Linkage moves smoothly without binding
  3. Step 3: Verify control oil pressure to the capacity regulator
    Control pressure meets the manufacturer specification

How to Reset

To reset: Repair the capacity control system, then reset the fault on the controller.