Bitzer Screw Compressor CSH/CSN Error Code AL4

Bitzer Refrigeration Major Pressure

Model: Screw Compressor CSH/CSN | Code: AL4

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports low suction pressure. The suction pressure has dropped below the minimum safe operating threshold.

Possible Causes

  • Low refrigerant charge from system leak
  • Evaporator airflow restricted or iced
  • Expansion valve malfunction or blockage

Troubleshooting Steps

  1. Step 1: Check suction pressure against the refrigerant saturation chart
    Pressure corresponds to the correct evaporation temperature
  2. Step 2: Inspect evaporator for ice or restricted airflow
    Evaporator is clean and airflow is normal
  3. Step 3: Test expansion valve operation and superheat setting
    Valve maintains correct superheat

How to Reset

To reset: Raise suction pressure above the threshold, then acknowledge the alarm.

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH

Category: Refrigeration