Bitzer Screw Compressor CSH/CSN Error Code AL8

Bitzer Refrigeration Critical Power

Model: Screw Compressor CSH/CSN | Code: AL8

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports a phase loss fault. One of the three supply phases is missing, preventing safe motor operation.

Possible Causes

  • Blown fuse or tripped breaker on one phase
  • Loose or corroded connection on one conductor
  • Broken wire or damaged cable in the supply circuit

Troubleshooting Steps

  1. Step 1: Check voltage on all three phases at the compressor terminals
    All three phase voltages are present and balanced
  2. Step 2: Trace the missing phase back to the disconnect or breaker
    Open fuse or loose connection is found and repaired
  3. Step 3: Verify motor winding resistance is balanced across all phases
    Resistance values are within 2 percent of each other

How to Reset

To reset: Restore all three phases, then reset the phase monitoring relay.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH