Bitzer Screw Compressor CSH/CSN Error Code AL8

Bitzer Refrigeration Critical Power

Model: Screw Compressor CSH/CSN | Code: AL8

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports a phase loss fault. One of the three supply phases is missing, preventing safe motor operation.

Possible Causes

  • Blown fuse or tripped breaker on one phase
  • Loose or corroded connection on one conductor
  • Broken wire or damaged cable in the supply circuit

Troubleshooting Steps

  1. Step 1: Check voltage on all three phases at the compressor terminals
    All three phase voltages are present and balanced
  2. Step 2: Trace the missing phase back to the disconnect or breaker
    Open fuse or loose connection is found and repaired
  3. Step 3: Verify motor winding resistance is balanced across all phases
    Resistance values are within 2 percent of each other

How to Reset

To reset: Restore all three phases, then reset the phase monitoring relay.

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH

Category: Refrigeration