Bitzer Screw Compressor CSH/CSN Error Code AL6

Bitzer Refrigeration Critical Motor

Model: Screw Compressor CSH/CSN | Code: AL6

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports motor overload. The motor current has exceeded the rated full-load value for the protection trip delay.

Possible Causes

  • Compressor operating beyond design conditions
  • Low supply voltage causing elevated motor current
  • Motor winding degradation or partial short

Troubleshooting Steps

  1. Step 1: Check motor current with a clamp meter against nameplate FLA
    Current does not exceed rated full load amps
  2. Step 2: Verify supply voltage at the motor terminals under load
    Voltage is within 10 percent of rated value
  3. Step 3: Perform insulation resistance test on motor windings
    Insulation resistance exceeds minimum standard

How to Reset

To reset: Clear the overload, allow the motor to cool, then reset the overload relay.