Bitzer Screw Compressor CSH/CSN Error Code AL3

Bitzer Refrigeration Major Temperature

Model: Screw Compressor CSH/CSN | Code: AL3

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports high oil temperature. The lubricating oil temperature has exceeded the safe operating limit.

Possible Causes

  • Oil cooler fouled or cooling water flow insufficient
  • High discharge temperature transferring heat to the oil system
  • Excessive friction from bearing wear generating heat

Troubleshooting Steps

  1. Step 1: Inspect the oil cooler and verify cooling medium flow
    Cooler is clean and flow rate meets specification
  2. Step 2: Verify discharge temperature is within normal limits
    Discharge temperature is below the alarm setpoint
  3. Step 3: Check bearing condition through oil analysis
    Oil sample shows no excessive metal particles

How to Reset

To reset: Reduce oil temperature below the threshold, then clear the alarm on the controller.

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH

Category: Refrigeration