Bitzer Screw Compressor CSH/CSN Error Code AL3

Bitzer Refrigeration Major Temperature

Model: Screw Compressor CSH/CSN | Code: AL3

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports high oil temperature. The lubricating oil temperature has exceeded the safe operating limit.

Possible Causes

  • Oil cooler fouled or cooling water flow insufficient
  • High discharge temperature transferring heat to the oil system
  • Excessive friction from bearing wear generating heat

Troubleshooting Steps

  1. Step 1: Inspect the oil cooler and verify cooling medium flow
    Cooler is clean and flow rate meets specification
  2. Step 2: Verify discharge temperature is within normal limits
    Discharge temperature is below the alarm setpoint
  3. Step 3: Check bearing condition through oil analysis
    Oil sample shows no excessive metal particles

How to Reset

To reset: Reduce oil temperature below the threshold, then clear the alarm on the controller.

Comments (0)

Share your experience to help others facing the same problem.

No comments yet. Be the first to share your experience!

Leave a Comment

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH

Category: Refrigeration