Bitzer Screw Compressor CSH/CSN Error Code AL12

Bitzer Refrigeration Major Lubrication

Model: Screw Compressor CSH/CSN | Code: AL12

Applicable Systems
Octagon 4-Comp

Symptoms

The compressor reports a low oil level alarm. The oil level in the separator is below the minimum safe level.

Possible Causes

  • Oil carried out with refrigerant due to low gas velocity
  • System leak causing oil loss over time
  • Oil separator demister damaged allowing oil carry-over

Troubleshooting Steps

  1. Step 1: Check oil level in the separator sight glass
    Oil level is at or above the minimum mark
  2. Step 2: Inspect the system for leaks and repair as needed
    No active leaks detected in the system
  3. Step 3: Check the oil separator demister for damage
    Demister is intact and functioning correctly

How to Reset

To reset: Add approved oil to the proper level, then clear the alarm on the controller.

Source: Bitzer Screw Compressor Operating Instructions, Bitzer Kuhlmaschinenbau GmbH

Category: Refrigeration