Applicable Systems
VRV IV-S

Symptoms

The air conditioner reports a room temperature sensor fault. The indoor unit room temperature sensor is reading incorrectly.

Possible Causes

  • Thermistor element drifted from calibration
  • Sensor wiring damaged or connector loose
  • Sensor element open or shorted

Troubleshooting Steps

  1. Step 1: Test the thermistor resistance at the current temperature
    Resistance matches the manufacturer chart
  2. Step 2: Check the sensor wiring and connector
    Wiring is intact and connector is secure
  3. Step 3: Replace the faulty sensor if out of specification
    New sensor reads correctly

How to Reset

To reset: Replace the faulty sensor, then clear the fault from the controller.

Source: Daikin Air Conditioner Service Manual, Daikin Industries Ltd.