Mitsubishi GOT2000 Series Error Code ERR-405

Mitsubishi HMI Critical Hardware

Model: GOT2000 Series | Code: ERR-405

Applicable Systems
GOT2000 Series

Symptoms

GOT2000 does not power on; 24 VDC applied but no backlight or beep.

Possible Causes

  • Internal 5 VDC and 3.3 VDC regulator failure on the GOT mainboard.
  • Blown onboard fuse due to accidental 220 VAC misconnection.
  • Power connector pin assignment reversed (L+/M swapped).

Troubleshooting Steps

  1. Step 1: Measure 24 VDC at the GOT terminal block and verify polarity with the silkscreen labels.
    Voltage is 21.6–26.4 VDC and L+/M are wired correctly.
  2. Step 2: Check the onboard fuse near the power entry connector for continuity.
    Fuse is continuous or replacement restores power LED.
  3. Step 3: Probe the 5 VDC and 3.3 VDC test points on the mainboard with an oscilloscope.
    Both rails are stable within +/-5% with <50 mV ripple.

How to Reset

Replace the power entry fuse or the mainboard regulator module, and verify DC rail stability.

Common Replacement Parts

  • Onboard fuse 3.15 A: Onboard fuse 3.15 A
  • DC-DC regulator module: DC-DC regulator module

Source: Mitsubishi GOT2000 Series Hardware Installation Manual

Category: HMI