Mitsubishi GOT2000 Series Error Code ERR-406

Mitsubishi HMI Minor Memory

Model: GOT2000 Series | Code: ERR-406

Applicable Systems
GOT2000 Series

Symptoms

Alarm history shows duplicate entries with identical timestamps every second.

Possible Causes

  • Alarm trigger bit in the PLC ladder logic chattering due to marginal sensor threshold.
  • GOT alarm collection cycle set too fast (e.g., 100 ms) for the process dynamics.
  • Alarm display filter 'Combine same alarms' disabled in the project settings.

Troubleshooting Steps

  1. Step 1: Monitor the PLC trigger bit with GX Works3 and add a one-shot or hysteresis.
    Bit transitions only once per true alarm event.
  2. Step 2: Increase the GOT alarm sampling interval to 1 second or match the PLC scan.
    Duplicate entries cease and each alarm appears only once per occurrence.
  3. Step 3: Enable the 'Combine same alarms' option in GT Designer3 alarm display settings.
    Consecutive identical alarms are grouped into a single line with a count badge.

How to Reset

Add hysteresis to the PLC alarm trigger, slow the GOT sampling rate, and enable alarm combining.

Source: Mitsubishi GT Designer3 Alarm Function Manual

Category: HMI