Mitsubishi GOT2000 Series Error Code ERR-413

Mitsubishi HMI Critical Power

Model: GOT2000 Series | Code: ERR-413

Applicable Systems
GOT2000 Series

Symptoms

The HMI power supply voltage has dropped below the minimum 19.2V DC (for a 24V system). The display flickers and the HMI may reboot unexpectedly.

Possible Causes

  • Power supply output voltage low due to overload or failure
  • Wiring resistance too high from long cable runs or undersized conductors
  • Loose terminal connection causing voltage drop under load
  • Power supply filter capacitor degraded causing ripple and brownout

Troubleshooting Steps

  1. Step 1: Measure the voltage at the HMI power input terminals with a multimeter
    Voltage should be 20.4-28.8V DC; if below 19.2V, investigate the supply
  2. Step 2: Measure the voltage at the power supply output terminals
    If the supply reads 24V but the HMI reads low, check the wiring for voltage drop
  3. Step 3: Inspect all power wiring connections for tightness and corrosion
    Tighten loose terminals and clean corroded contacts
  4. Step 4: If the power supply is overloaded, check the total load against its rating
    Add a dedicated supply or upgrade the capacity if overloaded

How to Reset

Reset: The HMI reboots automatically once the supply voltage is restored above 20.4V DC.

Common Replacement Parts

  • Power supply: 24V DC, 50W, DIN-rail mount (Match output current to total HMI load)
  • Power cable: 18 AWG, 2-core, shielded (Keep length under 30m to minimize voltage drop)

Frequently Asked Questions

  • Q: What causes voltage drop in HMI wiring?

    Long cable runs, undersized wire, and loose terminals. Calculate drop using V=2RLI/A where R is copper resistivity.

  • Q: Can I use the PLC power supply for the HMI?

    Only if the supply has sufficient spare capacity. A dedicated supply is preferred to isolate HMI noise from the PLC.

  • Q: What is the HMI power consumption?

    Typically 10-30W depending on screen size and backlight. Check the manual for the specific model.