- GP-Pro EX display unit shows error RHAA013: COM1 9th pin has not been set to VCC (5V Power Supply).
Applicable Systems
GP4000 Series
Symptoms
Possible Causes
- The 9th pin of COM1 is connected as RI input (e.g. when using an Isolation Unit RS-232C Type).
Troubleshooting Steps
- Step 1: Designate RI in the RI/VCC settings of GP-Pro EX Device/PLC.
Communication restored and error cleared
How to Reset
Repower or reset the display unit after correcting the root cause.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Pro-face GP-Pro EX Maintenance/Troubleshooting Manual, T.7.1 Common Display errors (proface.tech/otasuke official)