Applicable Systems
G3 Series
Symptoms
Data logging stops intermittently; log file timestamps show gaps of several hours.
Possible Causes
- SD card write-protect switch accidentally engaged, causing write failures.
- Log file size exceeds 2 GB on a FAT32 volume, preventing further appends.
- Crimson logging task priority too low, preempted by frequent screen refreshes.
Troubleshooting Steps
- Step 1: Inspect the SD card physical write-protect tab position.
Tab is in the unlocked position and the lock sensor reads open. - Step 2: Check the largest log file size in the Crimson file manager.
No single file exceeds 1.8 GB and automatic file rotation is enabled. - Step 3: Increase the logging task priority in Crimson task configuration.
No timestamp gaps >1 minute appear during a 24-hour continuous test.
How to Reset
Unlock the SD card, enable automatic log rotation, and raise the logging task priority.
Comments (0)
Share your experience to help others facing the same problem.
Leave a Comment
Source: Red Lion Graphite Data Logging Application Note