Copeland Copeland Scroll Compressor (CoreSense/Comfort Alert) Error Code E17

Copeland Refrigeration Critical Power

Model: Copeland Scroll Compressor (CoreSense/Comfort Alert) | Code: E17

Applicable Systems
Copeland Scroll Compressor (CoreSense/Comfort Alert)

Symptoms

The compressor reports a phase sequence protection trip. The controller has detected incorrect phase rotation and locked out the compressor start.

Possible Causes

  • Power supply phase sequence changed by utility work
  • Wiring modification during maintenance altered the phase order
  • Phase loss causing single-phase operation

Troubleshooting Steps

  1. Step 1: Verify phase sequence at the compressor disconnect with a rotation tester
    Correct L1-L2-L3 sequence is confirmed
  2. Step 2: Check for any open fuses or broken conductors in the supply
    All three phases have equal voltage
  3. Step 3: Correct the wiring if the phase sequence is wrong
    Phase rotation tester shows correct sequence

How to Reset

To reset: Correct the phase sequence and verify all three phases, then cycle the compressor power.

Source: Copeland Scroll Compressor Service Manual, Emerson Climate Technologies

Category: Refrigeration