Symptoms

Motor current exceeded the allowable current limit: 2 x minimum(p0640, 4 x p0305 x p0306) >= 2 x p0305 x p0306.

Possible Causes

  • Motor parameters (P0305-P0311) set incorrectly
  • Process parameters (current limit P0640, ramp times P1120/P1121) set incorrectly
  • Drive hardware circuit fault (current detection / power module / trigger circuit)
  • Motor winding or cable short circuit or low insulation
  • Motor winding star/delta connection error
  • Inter-turn short circuit in motor winding
  • Mechanical jam or load surge

Troubleshooting Steps

  • Confirm motor nameplate data matches P0305-P0311 settings
  • Adjust P0640, P1120, P1121 according to process requirements
  • If fault occurs on power-up only, check drive hardware circuit
  • Disconnect motor cable and test - if fault clears, check motor winding/cable insulation
  • Check motor winding star/delta connection
  • For conveyor applications, check if fault occurs at specific positions - inspect mechanical parts
  • If load surge is unavoidable, increase P0640 or select larger drive

How to Reset

Reset by: 1) Correct the fault condition. 2) Press RESET button or send reset command via communication. 3) Verify fault does not recur during operation.