Symptoms

PROFINET communication fault - drive did not receive controller telegrams within PROFINET monitoring time.

Possible Causes

  • PROFINET controller stopped or abnormal
  • PROFINET network data refresh time too short
  • Communication cable broken or plug loose
  • Electromagnetic interference on PROFINET line

Troubleshooting Steps

  • Check PROFINET controller status
  • Extend PROFINET network data refresh time if many stations
  • Check communication cable for breaks or loose plugs
  • Check PROFINET port for damage
  • Use Siemens dedicated PROFINET cable, replace ordinary network cable
  • Verify proper grounding of PROFINET controller and drive
  • Keep PROFINET cable >20cm from power cables, max 100m length
  • To suppress: P2118[x]=8501, P2119[x]=3 (may prevent normal stop - set emergency stop)

How to Reset

Reset by: 1) Correct the fault condition. 2) Press RESET button or send reset command via communication. 3) Verify fault does not recur during operation.

Source: Siemens SINAMICS G120 Common Faults Manual (ad.siemens.com.cn)