Symptoms
Hardware current limit responded too frequently in each phase. Allowable excess depends on power unit type.
Possible Causes
- Closed-loop control parameters set incorrectly
- Motor or power cable fault
- Power cable exceeds maximum allowable length
- Motor load too large
- Power unit damaged
- Load surge
Troubleshooting Steps
- Verify motor data parameters are correct
- Check motor connection (star/delta)
- Check power cable connections
- Check power cable for short circuit or ground fault
- Verify power cable length within limits
- Replace power unit if damaged
- Check motor load conditions
How to Reset
Reset by: 1) Correct the fault condition. 2) Press RESET button or send reset command via communication. 3) Verify fault does not recur during operation.